Arc Flash Risk Assessment: Beyond the Formula (IEEE 1584)

November 2, 2025 Design Calculators Engineering Team 18 min read Electrical Safety

Calculating incident energy is more than just plugging numbers into software. It is a life-safety discipline. We analyze why 1.2 cal/cm² is the critical threshold, how electrode orientation changes the physics of the arc, and why the clearing time of your upstream breaker is the single most important variable in saving lives.

If you have ever stood in front of a 480V or 415V switchboard while a technician racks in a breaker, you have felt the tension in the room. There is a primal understanding that inside that metal box, tremendous energy is waiting for a path to ground. An arc flash is not just a spark; it is a violent explosion of energy, light, and molten metal that can reach temperatures of 35,000°F (19,400°C)—hotter than the surface of the sun.

For decades, the engineering community relied on basic tables to estimate this risk. However, with the adoption of IEEE 1584-2018, the mathematics behind Arc Flash Risk Assessment has evolved into a precise science. Yet, too many engineers treat this assessment as a "checkbox" exercise—running a report, printing a label, and walking away. This approach is dangerous.

To truly protect personnel, we must look beyond the formula. We need to understand the physical behaviors of arcing faults, the nonlinear relationship between working distance and burn severity, and the often-overlooked interaction between protection settings and incident energy.

The 1.2 cal/cm² Threshold: Why It Matters

The entire concept of Arc Flash Risk Assessment revolves around a single, critical number: 1.2 cal/cm². This is not an arbitrary safety margin; it is a biological limit.

1.2 cal/cm² is the amount of thermal energy required to cause the onset of a second-degree burn on unprotected human skin. It is the point where the skin blisters and the damage becomes permanent. If your calculations show an incident energy of 1.2 cal/cm² at the working distance, the PPE you select is not designed to keep you cool or comfortable—it is designed to limit your injury to a survivable second-degree burn, preventing third-degree burns that destroy nerves and muscle tissue.

The Physics of the Arc: It’s Not Just a Short Circuit

Many engineers confuse a "Bolted Fault" with an "Arcing Fault." A bolted fault occurs when conductors are physically joined (like a wrench dropped across busbars), resulting in the maximum possible current flow. The impedance is near zero, and the current is massive. Paradoxically, bolted faults are often safer from an arc flash perspective because the massive current trips the upstream breaker instantaneously.

An Arcing Fault is different. It travels through the air. Air is an insulator, which means the arc has impedance. This impedance reduces the current flow, often to 40% or 50% of the bolted fault current. This reduction is the deadly trap.

If your upstream breaker is set to trip instantaneously at 20,000 Amps, but the arcing fault only produces 15,000 Amps due to air impedance, the breaker will not trip instantly. It will wait for its "Short Time Delay" setting—perhaps 0.3 or 0.5 seconds. In the world of arc flash, 0.5 seconds is an eternity. The energy release during that delay can increase the incident energy from a manageable 2 cal/cm² to a lethal 40 cal/cm².

Calculate Short Circuit Current

The "Working Distance" Factor: The Inverse Square Law

One of the variables often input casually into assessment software is "Working Distance." This is the distance from the prospective arc source (the busbars) to the worker's face and chest.

  • Low Voltage (MCCs & Panels): Typically 18 inches (457 mm).
  • Medium Voltage (Switchgear): Typically 36 inches (914 mm).

However, physics dictates that thermal energy radiates spherically. The intensity of that energy follows the Inverse Square Law. If you cut the distance to the arc in half, the energy received increases by a factor of four.

Consider a technician troubleshooting a panel. The label says the incident energy is 6 cal/cm² at 18 inches. But if that technician leans in to inspect a wire, reducing their distance to 9 inches, the exposure is no longer 6 cal/cm²—it is closer to 24 cal/cm². A standard Category 2 arc flash suit (rated 8 cal/cm²) would fail catastrophically in this scenario.

The Danger of "Reaching In"

This is why modern safety protocols emphasize "remote racking" and using extended tools. Every inch of distance you can put between the busbar and your body exponentially increases your survival capability. When verifying tools or designs, ensure that the Working Distance reflects the actual ergonomic reality of the task, not just the default value in the standard.

Electrode Configuration: The 2018 Game Changer

Prior to the 2018 update of IEEE 1584, arc flash calculations generally assumed a "Vertical Open Air" orientation. The 2018 standard introduced five distinct electrode configurations that fundamentally change how we calculate energy. This change acknowledged that the direction of the plasma blast matters as much as the energy itself.

  1. VCB (Vertical Electrodes in a Metal Box): This is the standard configuration for most MCCs and panels. The arc travels down, but the plasma hits the bottom of the box and blasts outward toward the worker.
  2. VCBB (Vertical Electrodes Terminating in a Barrier): Common in insulated case circuit breakers. The barrier amplifies the outward projection of energy.
  3. HCB (Horizontal Electrodes in a Metal Box): THE DANGER ZONE. This typically occurs where cables connect to the horizontal bus. The arc plasma is magnetically propelled directly out of the box, straight at the worker. HCB configurations often yield incident energy results 2-3 times higher than VCB for the same current.
  4. VOA (Vertical Open Air): Typical for outdoor pole-mounted overhead lines.
  5. HOA (Horizontal Open Air): Less common, specific outdoor orientations.

The Engineering Takeaway: If you are modeling a system and you simply default everything to "VCB," you are likely underestimating the risk at cable termination points. Identifying HCB locations is critical for an accurate risk assessment.

The Clearing Time: The Single Biggest Variable

While we cannot easily change the laws of physics or the fault current available from the utility transformer, we can control time. The duration of the arc is directly proportional to the total energy released. Total Energy = Power × Time.

If an arc lasts 0.1 seconds (6 cycles), the energy might be 1.5 cal/cm². If the breaker ignores the fault and lets it burn for 2 seconds, that energy becomes 30 cal/cm². This brings us to the most vital aspect of the assessment: Protective Device Coordination.

The Coordination Conflict

Electrical engineers often face a conflict between Selectivity and Safety.

  • Selectivity demands that we delay the upstream breaker to allow the downstream breaker to clear the fault first. This keeps the rest of the facility running.
  • Safety demands we trip the upstream breaker as fast as possible to limit arc energy.

Traditional "Selective Coordination" often results in high arc flash categories because upstream breakers are intentionally delayed. Modern solutions solve this paradox:

Modern Mitigation Technologies

1. Maintenance Mode Switches (ARMS):
A physical switch on the breaker door. When turned on, the breaker bypasses its delay timers and trips instantaneously on any fault. A worker flips this switch before opening the door, drastically lowering the PPE requirement during the task.

2. Zone Selective Interlocking (ZSI):
Breakers communicate with each other. If a feeder sees a fault but the main breaker does not receive a "blocking" signal from downstream, the main breaker knows the fault is in the busbar itself and trips instantly, ignoring its programmed delay.

3. Optical Arc Detection:
The fastest protection available. Light sensors inside the switchgear detect the blinding flash of the arc before the current even peaks. These relays can issue a trip signal in less than 1 millisecond.

Check Protection Device Settings

The "2-Second Rule" and Infinite Bus

When running calculations, two common pitfalls can skew results:

1. The Infinite Bus Assumption:
It is conservative to assume the utility is providing infinite fault current. For equipment duty ratings (kAIC), this is good. For Arc Flash, it is bad. As mentioned earlier, higher current usually trips breakers faster. By assuming infinite current, you might calculate a 0.05s trip time. In reality, the weaker utility connection might produce lower current that takes 0.5s to trip. Always model the "Minimum Fault Current" scenario.

2. The 2-Second Cutoff:
IEEE 1584 recommends capping the calculation duration at 2 seconds. The logic is that within 2 seconds, the arc will either self-extinguish as distances widen, or the pressure will blast the worker away from the source (a grim but practical assumption). However, relying on this 2-second cap to "pass" a label is irresponsible. If a fault is clearing in 2 seconds, the gear is effectively destroyed, and the room is filled with toxic metal vapor. The goal should be clearing times under 0.1 seconds.

A Practical Scenario: The 480V Panel Maintenance

Imagine a facility with a 2000A Main Switchboard feeding a 200A lighting panel. The engineer needs to tighten a loose connection in the lighting panel.

Scenario A (Poor Design):
The 200A feeder breaker in the main switchboard has a fixed magnetic trip unit set high (to avoid nuisance tripping). An arc fault occurs in the lighting panel. The current is too low to trip the main feeder instantly. The fault burns for 1.5 seconds until the main transformer primary fuse blows.
Result: Incident Energy > 40 cal/cm². Explosion. Fatal.

Scenario B (Optimized Design):
The engineer calculated the arcing current at the lighting panel (approx. 2.5kA). They adjusted the "Instantaneous" pickup of the 200A feeder breaker down to 1500A. Now, the breaker sees the 2.5kA arc and trips in 0.03 seconds.
Result: Incident Energy < 0.5 cal/cm². Minor spark. Scared technician, but alive and uninjured.

This is why simply buying "Arc Rated" clothing is not the solution. The solution is in the settings of the relays and breakers.

Conclusion: Safety is a Calculated Decision

Arc Flash Risk Assessment is not about generating a sticker; it is about understanding the energy flow in your facility. It requires a holistic view that combines short circuit analysis, protective device coordination, and realistic working conditions.

The IEEE 1584 standard gives us the math, but the engineer provides the wisdom. By verifying electrode configurations, validating clearing times against minimum fault currents, and implementing technologies like Maintenance Mode switches, we move beyond the formula and into the realm of true engineered safety.

Do not guess when it comes to incident energy. Use validated tools to model your system, check your protective device settings, and always verify the "Working Distance" before opening that door.

Ready to Analyze Your System?

Use our suite of free engineering calculators to verify your protection settings and estimate incident energy: