1. Fundamentals of Generator Sizing and Physics
Sizing a generator correctly is one of the most critical aspects of electrical power system design. Unlike utility power, which is essentially an infinite bus capable of absorbing massive current spikes without voltage deviation, a generator is a finite source with limited mechanical and electrical inertia. When you ask a generator to start a large motor or power a non-linear load, the physics of the machine—specifically the interaction between the diesel engine (prime mover) and the alternator (electrical end)—dictates the outcome.
The primary constraints are Thermal Capacity (how much heat the windings can take, determining the kW/kVA rating) and Transient Reactance (how much the voltage drops when sudden load is applied). The generator must be sized to handle the steady-state running load without overheating, but it must also possess enough magnetic reserve in the alternator to handle inrush currents without collapsing the voltage field.
Where $\eta_{alt}$ is alternator efficiency (typically 90-95%). The engine provides real power (kW), while the alternator provides the KVA and the reactive capability (kVAR). This is why a generator engine might not bog down, but the voltage can still collapse if the alternator is undersized.
2. ISO 8528 Ratings: Prime vs. Standby
Understanding the standard ratings defined by ISO 8528-1 is essential for commercial specification. Misapplying these ratings can lead to warranty voiding or premature failure.
- Standby Power (ESP): The maximum power available during a variable electrical power sequence, under the stated operating conditions, for which a generating set is capable of delivering in the event of a utility power outage. It is typically limited to 200-500 hours per year, with no overload capability. This is the rating most backup generators use.
- Prime Power (PRP): The maximum power which a generating set is capable of delivering continuously while supplying a variable electrical load. The generator can run 24/7/365 at varying loads (usually 70% average). It typically includes a 10% overload capability for 1 hour in every 12 hours of operation.
- Continuous Power (COP): The power available for an unlimited number of hours at a constant 100% load. This is rare and used for base-loading power plants.
Design Tip: A generator rated 500 kVA Standby is essentially the same machine as one rated 450 kVA Prime. The difference is the allowed thermal stress profile. If you are designing for a construction site (Prime application), you must derate the machine compared to a hospital backup (Standby application).
3. The Physics of Motor Starting (Transient Analysis)
The most challenging event for a generator is starting a large AC induction motor. When a motor starts Direct-On-Line (DOL), it acts like a short circuit transformer secondary. The rotor is locked (stationary), and the "Locked Rotor Current" (LRA) can be 6 to 7 times the Full Load Amps (FLA).
Transient Voltage Dip (TVD)
When this massive current surge hits, the generator's internal impedance causes an instantaneous voltage drop. According to Ohm’s Law for AC circuits:
Where $X''_d$ is the generator's sub-transient reactance. If the voltage drops below 15-30% (depending on the contactor rating), motor contactors may chatter or drop out, causing the motor to fail to start. This calculator uses a simplified "Start Factor" to ensure the generator kVA is sufficient to keep voltage dip within acceptable limits (typically < 30%).
NEMA Codes
Motors have NEMA Code letters indicating their kVA/HP at startup. Code G (typical) draws ~6 kVA per HP. Code L might draw ~9 kVA per HP. While this tool simplifies the input to "Surge kW", professional engineers calculate this precisely using the NEMA code.
4. Non-Linear Loads and Harmonics (IEEE 519)
Modern commercial loads are increasingly "non-linear." This includes UPS systems, Variable Frequency Drives (VFDs), LED drivers, and computer power supplies. Unlike resistive heaters, these devices draw current in pulses rather than smooth sine waves.
These pulses distort the voltage waveform, creating Total Harmonic Distortion (THD). High THD causes heating in the generator alternator windings. To mitigate this:
- Oversizing: We typically oversize the alternator by 20-25% (or use a lower temperature rise alternator, e.g., 80°C or 105°C rise) to handle the skin effect heating caused by harmonics.
- Impedance: Lower impedance alternators (larger kVA) are "stiffer" sources and resist waveform distortion better.
This calculator applies a Harmonic Factor (1.25x) when you select "Non-Linear Load" to emulate this necessary upsizing per IEEE 519 guidelines.
5. Environmental Derating
Generators breathe air. Diesel engines need oxygen for combustion, and alternators need air for cooling. Manufacturers rate generators at Standard Reference Conditions (usually 25°C or 27°C, and 100-150m altitude). Deviating from this requires derating:
- Altitude: Air becomes less dense (lower partial pressure of O2) as you go up. Turbochargers help, but generally, expect ~3-4% power loss for every 300m above 1000m.
- Temperature: Hot air is less dense and provides less cooling. Expect ~1-2% loss for every 5°C above rated ambient (usually 40°C or 50°C for industrial sets).
Failing to account for a 40°C day on a rooftop in Denver (high altitude) could result in a generator that shuts down on "Under Frequency" or "Over Temperature" just when it's needed most.
6. Fuel Systems and Operational Cost
Fuel consumption is largely linear with load, but efficiency drops at low loads. A diesel engine is most efficient at 70-80% load.
Wet Stacking
Running a diesel generator below 30% load for extended periods causes "wet stacking"—unburned fuel and soot accumulate in the exhaust system because the cylinder temperature is too low for complete combustion. This can glaze cylinder liners and destroy the engine. This is why sizing a generator "too big" "just to be safe" is poor engineering practice. The generator should be sized so the base load is at least 30-40% of its rating.
Fuel Types
- Diesel: High energy density, long shelf life (with treatment), standard for mission-critical (data centers, hospitals).
- Natural Gas: Infinite run time (utility pipe), cleaner burn, but lower transient response (step load capability) compared to diesel.
- Propane (LPG): Good for residential, indefinite shelf life of fuel, but tank size limits run time.
7. Installation Best Practices
Beyond sizing, successful implementation involves:
- Grounding: Determining whether the generator neutral should be bonded to the frame or floating depends on whether the transfer switch is 3-pole (solid neutral) or 4-pole (switched neutral). This is critical for Ground Fault protection.
- Vibration Isolation: Generators shake. Spring isolators are mandatory to prevent structural damage to the building.
- Sound Attenuation: 75 dBA at 7 meters is standard, but hospitals often require 65 dBA critical grade silencers and enclosures.