Harmonic Signature Identifier & Waveform Builder

Comprehensive Power Quality Studio. Mode 1: Upload raw current data to diagnose sources (VFD/SMPS/Saturation). Mode 2: Synthesize waveforms from scratch by adjusting harmonic sliders to visualize distortions and check IEEE 519 compliance in real-time.

Data Input
Harmonic Synthesis

Adjust sliders to inject harmonics relative to Fundamental (50Hz/60Hz).

3rd Harmonic (150/180Hz) 0%
5th Harmonic (250/300Hz) 0%
7th Harmonic (350/420Hz) 0%
9th Harmonic 0%
11th Harmonic 0%
13th Harmonic 0%
System Parameters

The Art of Harmonic Fingerprinting: A Comprehensive Guide

1. The Music of the Grid: What are Harmonics?

Imagine your electrical grid is an orchestra. The "Fundamental Frequency" (50Hz or 60Hz) is the deep, pure bass note that carries all the energy. It should be a smooth, perfect sine wave.

Harmonics are the unwanted overtones. They are integer multiples of that fundamental frequency (e.g., 150Hz, 250Hz, 300Hz). Just as overtones change the sound of an instrument from a pure whistle to a screechy violin, electrical harmonics distort the pure voltage sine wave into jagged, irregular shapes.

In power systems, we generally do not want this "music." These extra frequencies do no useful work; they only create heat, vibration, and interference. Understanding which "instrument" (load) is playing these bad notes is the art of Harmonic Fingerprinting.

2. The "Double-Hump" Camel: 6-Pulse Drives (VFDs)

Variable Frequency Drives (VFDs) are the workhorses of modern industry, controlling motors for pumps, fans, and conveyors. However, they are notorious harmonic generators.

The Mechanism: The input stage of a standard VFD is a 3-phase bridge rectifier made of 6 diodes. These diodes switch on and off in pairs to convert AC to DC. This switching action draws current in two distinct "humps" per half-cycle, rather than a smooth continuous flow.

The Math ($h = np \pm 1$): The harmonic orders produced by a rectifier are determined by the number of pulses ($p$). For a 6-pulse drive:
$$ h = 6(1) \pm 1 \Rightarrow 5^{th}, 7^{th} $$
$$ h = 6(2) \pm 1 \Rightarrow 11^{th}, 13^{th} $$

The Fingerprint: A spectrum dominated by the 5th (typically 25-35%) and 7th (10-15%) harmonics. If you see this pattern, look for a motor drive without a line reactor.

Why it matters: The 5th harmonic is a "Negative Sequence" harmonic. It creates a magnetic field in your motors that rotates backwards, fighting the motor's rotation. This causes intense overheating and vibration in motors powered by the same bus.

3. The "Shark Fin": Switch Mode Power Supplies (SMPS)

This profile belongs to the modern office: Server racks, PC workstations, and LED lighting. Unlike big industrial motors, these are single-phase electronic loads.

The Mechanism: An SMPS converts AC to DC using a capacitor. The diode bridge only conducts electricity when the grid voltage is higher than the voltage stored in the capacitor. This happens only at the very peak of the sine wave. The power supply takes a quick "gulp" of current at the top of the wave and then shuts off. The waveform looks like a thin shark fin.

The Fingerprint: Because the pulse is so narrow, it is incredibly rich in Triplen Harmonics (multiples of 3: 3rd, 9th, 15th). The 3rd harmonic can often exceed 70-80% of the fundamental!

The Neutral Danger: In a 3-phase Wye system, the fundamental currents (A, B, C) cancel each other out in the neutral wire. However, 3rd harmonics are "Zero Sequence"—they are all in phase with each other. Instead of canceling, they add up.
Result: You can measure 0 Amps on the phases but have the neutral wire glowing red hot with 1.73x phase current. This is a common cause of electrical fires in office buildings.

4. The "Lopsided" Wave: Transformer Saturation

Transformers are designed to operate within a specific magnetic limit. If you push them past this limit (during energization inrush or over-voltage events), the iron core "saturates."

The Mechanism: Think of the core as a bucket. Once it's full of magnetic flux, you can't pour more in. The relationship between Voltage and Current stops being linear. The current spikes disproportionately high on one side of the wave while remaining normal on the other, creating a lopsided, asymmetrical waveform.

The Fingerprint: Fourier analysis tells us that any asymmetrical waveform must contain Even Harmonics. A strong presence of the 2nd Harmonic (and sometimes 4th) is the definitive signature of saturation or inrush.

Protection Tip: Differential relays use this specific fingerprint (2nd Harmonic Restraint) to prevent tripping when you energize a transformer. If the relay sees high current + high 2nd harmonic, it knows it's just saturation, not a short circuit.

5. The "Chaos": Arc Furnaces & Welders

Electric Arc Furnaces (EAFs) used in steelmaking are among the most difficult loads to manage. They melt scrap metal by striking a massive electrical arc.

The Mechanism: An electric arc is violent and chaotic. The resistance of the arc changes thousands of times per second as the scrap metal melts and shifts. This chaotic draw creates distortion at every frequency, not just integer multiples.

The Fingerprint: A raised "noise floor" across the entire spectrum. Crucially, you will see Interharmonics (frequencies like 185Hz or 2.5th harmonic). This looks like "grass" or noise between the main harmonic bars.

Consequences: Interharmonics interact with the fundamental to create "beat frequencies" in the 1Hz–30Hz range. This frequency range is visible to the human eye, causing light bulbs to strobe or flicker (Voltage Flicker), which can induce nausea in humans.

6. Impact & Mitigation Strategies

  • Overheating: High frequency currents flow on the outer skin of conductors (Skin Effect), effectively reducing the wire size and increasing resistance. Mitigation: Oversize cables or use multi-strand conductors.
  • Resonance: If a harmonic frequency matches the resonant frequency of your power factor correction capacitors, they can explode. Mitigation: Install "Detuned Reactors" in series with capacitors.
  • K-Rated Transformers: Standard transformers overheat with harmonic loads. K-Rated transformers have beefier neutrals and special winding designs to handle the heat.
  • Active Filters: These advanced devices inject "anti-noise" (current equal and opposite to the harmonics) to cancel out distortion in real-time.