Harmonic Distortion: The Silent Killer of Power Capacitors

November 6, 2025 Design Calculators Engineering Team 15 min read Power Quality

It's a familiar story: a facility upgrades to efficient VFDs and LED lighting, only to find their main transformer overheating and their capacitor banks swollen or exploding. We explain the invisible threat of Harmonic Resonance, Total Harmonic Distortion (THD), and how to size a Detuned Reactor to save your equipment.

Modern industrial facilities are changing. The days of simple "linear" loads like induction motors and incandescent bulbs are gone. Today, we live in the era of Non-Linear Loads: Variable Frequency Drives (VFDs), UPS systems, LED drivers, and switching power supplies.

While these devices save energy, they come with a hidden cost: Harmonics. Unlike a standard load that draws a smooth sine wave of current, a VFD draws current in sharp pulses. These pulses distort the voltage waveform on the entire bus.

If you have ever walked into a switch room and heard a transformer humming significantly louder than usual, or noticed that your Power Factor Correction (PFC) capacitors are failing prematurely, you are likely a victim of harmonic distortion. But why do the capacitors fail first?

What is THD?

Total Harmonic Distortion (THD) is a measure of how "messy" your waveform is. In a 60Hz system:

  • Fundamental: 60Hz (The useful power).
  • 5th Harmonic: 300Hz (5 × 60). Often generated by 6-pulse VFDs.
  • 7th Harmonic: 420Hz (7 × 60).

These higher frequencies piggyback on the main wave. High THD causes skin-effect heating in cables and eddy current losses in transformers, de-rating their capacity significantly.

The Trap: Why Capacitors Hate Harmonics

This is where basic physics turns against us. The impedance (resistance to current flow) of a capacitor is inversely proportional to frequency:

X_c = 1 / (2 × π × f × C)

To a 60Hz signal, a capacitor looks like a high impedance. But to a 300Hz (5th harmonic) signal, that same capacitor looks like a short circuit! The capacitor becomes a "sink" for all the high-frequency garbage on the network. It tries to absorb these harmonic currents, leading to massive overheating, dielectric breakdown, and eventual explosion.

Calculate Your THD

The Nightmare Scenario: Parallel Resonance

It gets worse. Your facility has inductance ($L$) from the main transformer and cabling. You added capacitance ($C$) for power factor correction.
Whenever you have $L$ and $C$ in a circuit, you have a Resonant Frequency:

f_res = 1 / (2 × π × √LC)

If this natural resonant frequency happens to align with one of the harmonics present in your system (usually the 5th or 7th), you create a Parallel Resonance circuit. The impedance of the network rises to infinity, trapping the harmonic currents between the transformer and the capacitor bank. These currents oscillate back and forth, amplifying to 10 or 20 times their original value.

Result: Fuses blow, breakers trip, capacitors bulge, and the main transformer can overheat to the point of failure, even if it is only 60% loaded.

The Solution: Detuned Reactors

You cannot simply remove the capacitors; you need them to avoid power factor penalties. The solution is to change the physics of the capacitor bank by adding an inductor (Reactor) in series with the capacitor.

This creates a Detuned Capacitor Bank. The goal is to tune the $L-C$ circuit to a frequency that is below the lowest dominant harmonic.

How Sizing Works (The 7% Rule)

In a standard industrial environment dominated by 6-pulse drives, the 5th harmonic (300Hz at 60Hz, or 250Hz at 50Hz) is the biggest threat. We want to tune our resonance point to be safely below this.

  • 7% Reactor (Most Common): This tunes the circuit to roughly 189Hz (in a 50Hz system) or 227Hz (in a 60Hz system). This is safely below the 5th harmonic (250Hz/300Hz). At this frequency, the circuit acts as an inductor, blocking the harmonic currents from entering the capacitor, while still acting as a capacitor for the fundamental 50/60Hz frequency to correct power factor.
  • 14% Reactor: Used when the 3rd harmonic is present (high percentage of single-phase loads like lighting/computers).
  • 5.67% Reactor: A legacy standard, often tuned too close to the 5th harmonic for comfort in modern heavy-VFD sites.
Check for Resonance Risk

Practical Design Steps

If you are designing a PFC bank for a facility with VFDs:

  1. Assume Harmonics Exist: Unless the facility is purely resistive (heaters) or DOL motors, assume you have harmonics. Standard capacitors are a liability.
  2. Calculate Resonance: Use a calculator to see where your proposed capacitor kVAR and transformer kVA will resonate. If it lands near 250Hz, 300Hz, 350Hz, or 420Hz, do not install it.
  3. Specify Detuned Banks: Always specify "Detuned" or "Reactor-Protected" banks. The cost premium (approx. 30%) is negligible compared to the cost of replacing the bank every 12 months.
  4. Voltage Rating: When you add a reactor, the voltage across the capacitor terminal rises (Ferranti Effect). A 400V system with 7% reactors requires capacitors rated for at least 440V or 480V. Using 400V capacitors in a detuned bank ensures premature failure.

Conclusion: Protect Your Assets

Harmonic distortion is often invisible until it causes a catastrophic failure. The audible hum of a transformer or the bulging of a capacitor can are distress signals.

By understanding the interaction between Inductance ($L$) and Capacitance ($C$), you can design systems that are immune to resonance. Never install "plain" capacitors in a VFD-rich environment. Always detune, always check the resonant frequency, and treat Power Factor Correction as a tuned filter, not just a battery of cans.

Analyze Your Power Quality

We provide tools to help you identify resonance risks and calculate distortion levels: